Connecting a weighing indicator to a PLC over RS-485 Modbus RTU
Most lines that send weight to a PLC or HMI use RS-485 Modbus RTU. First check which interface your model has, then work through the settings below when the link does not respond.
Built in or optional
| Model | Built in | Options | Typical use |
|---|---|---|---|
| BDI-2033 (DIN rail) | OP-02B RS-485 Modbus RTU | OP-04 BCD output | Inside a control cabinet, weight to PLC |
| BDI-2033C (DIN rail) | OP-02B RS-485 Modbus RTU, OP-01 I/O (10 in, 10 out) | OP-04 BCD output | Communication plus I/O control |
| BDE-2007 (panel) | OP-02A1 RS-232 (two ports) | OP-02B RS-485 Modbus RTU, OP-01, OP-05, OP-06, OP-08 | Panel mount with local display |
| BDI-2001B (desk) | OP-02A1 RS-232 | OP-02B RS-422/485, OP-03 printer, OP-05, OP-06, OP-08 | Weighbridges and large platforms |
A BDE-2007 labelled only OP-02A1 has no RS-485 Modbus RTU. Add option OP-02B.
When the PLC gets no valid reply
- Match baud rate, data bits, parity and stop bits on both ends.
- Set the command mode to Modbus. BDI-2033 and BDI-2033C can run in ASCII command mode or Modbus mode.
- Match the slave ID. Every device on one RS-485 line needs its own ID.
- Check wiring: A and B not swapped, shield grounded at one end, termination resistors on long lines.
- Check the register address, length and function code against the register map.
Several scales into one PLC
For hoppers and batching tanks, a common layout is one weight transmitter per scale, each with its own slave ID, all on one RS-485 line polled by the PLC. BDI-2033 and BDI-2033C mount side by side on a DIN rail and each takes up to 8 load cells of 350 ohm.
Frequently asked questions
What does Invalid Response mean in MODSCAN?
A reply arrived but in the wrong format. The usual causes are mismatched serial settings, the indicator not in Modbus command mode, or a wrong slave ID or register address.